1-14 BE1-67 General Information 9170900990 Rev HThree-Phase UnitsWhen targets are specified by the style number, internally operated targets are included to indicate thephase elements (A, B, C) involved in the tripping of the relay. Additionally, either internally operated orcurrent operated targets (as selected) indicate the function (time or instantaneous) that caused tripping.Output CircuitsResistive Ratings120 Vac: Make, break, and carry 7 Aac continuously250 Vdc: Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously, and break 0.3 Adc500 Vdc: Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously, and break 0.3 AdcInductive Ratings120 Vac, 125 Vdc, 250 Vdc: Break 0.3 A (L/R = 0.04)IsolationIn accordance with IEC 255-5 and ANSI/IEEE C37.90, one minute dielectric (high potential) tests asfollows:All circuits to ground: 2,121 VdcInput to output circuits: 1,500 Vac or 2,121 VdcUL RecognizedUL recognized per Standard 508, UL File No. E97033. Note: Output contacts are not UL recognized forvoltages greater than 250 volts.GOST-RGost-R certified No. POCC US.Me05.B03391; complies with the relevant standards of Gosstandart ofRussia. Issued by accredited certification body POCC RU.0001.11ME05.Surge Withstand CapabilityQualified to ANSI/IEEE C37.90.1-1989, Standard Surge Withstand Capability (SWC) Tests for ProtectiveRelays and Relay Systems.Operating TemperatureThe operating temperature range is from -40°C (-40°F) to +70°C (+158°F).Storage TemperatureThe storage temperature range is from -65°C (-85°F) to +100°C (+212°F).ShockIn standard tests, the relay has withstood 15 g in each of three mutually perpendicular planes withoutstructural damage or degradation of performance.VibrationIn standard tests, the relay has withstood 2 g in each of three mutually perpendicular planes, swept overthe range of 10 to 500 Hz for a total of six sweeps, 15 minutes each sweep without structural damage ordegradation of performance.www . ElectricalPartManuals . com