Manual 2100-592CPage 43 of 69TABLE 11W30G Indoor Blower Performance @ 230 and 460 VoltsRecommended W30G cooling airflow range at rated 1000 CFM @ 0.35 ESP (WC) is 820 – 1150 CFMFactory set on medium speed for cooling and for heating.Voltage adjustment – Reduce airflow by 100 CFM for 208 VoltDehumidification coil adjustment – Reduce airflow by 35 CFM for dehumidification coil installedTop outlet adjustment – Increase airflow by 50 CFM for top outlet modelsSG-3, RG-3, non-ducted application adjustment – Reduce airflow by 100 CFM for SG-3 and RG-3 installationsESPInchesH2OCOOLING MODE MANUAL FAN and HEATING MODEWet Coil 90,000 BTU Input 81,000 BTU InputHigh Medium Low High Medium Low High Medium Low0.0 - - - - - - 1060 1560 1350 1120 1560 1350 11200.1 - - - - - - 1000 1470 1260 1060 1470 1260 10600.2 - - - 1160 950 1370 1200 1010 1370 1200 10100.3 - - - 1080 880 1290 1120 940 1290 1120 9400.4 1150 990 - - - 1190 1030 860 1190 1030 8600.5 1050 910 - - - 1090 950 780 1090 950 7800.6 940 - - - - - - 980 840 660 980 840 660ESPInchesH2OCOOLING MODE MANUAL FAN and HEATING MODEWet Coil 68,000 BTU Input 61,000 BTU InputHigh Medium Low High Medium Low High Medium Low0.0 - - - - - - 1060 1560 1350 1120 1560 1350 11200.1 - - - - - - 1000 1470 1260 1060 1470 1260 10600.2 - - - 1160 950 1370 1200 1010 1370 1200 10100.3 - - - 1080 880 1290 1120 940 1290 1120 9400.4 1150 990 - - - 1190 1030 860 1190 1030 8600.5 1050 910 - - - 1090 950 780 1090 950 7800.6 940 - - - - - - 980 840 660 980 840 660ESPInchesH2OCOOLING MODE MANUAL FAN and HEATING MODEWet Coil 45,000 BTU Input 41,000 BTU InputHigh Medium Low High Medium Low High Medium Low0.0 - - - - - - 1060 1560 1350 1120 1560 1350 11200.1 - - - - - - 1000 1470 1260 1060 1470 1260 10600.2 - - - 1160 950 1370 1200 1010 1370 1200 10100.3 - - - 1080 880 1290 1120 940 1290 1120 9400.4 1150 990 - - - 1190 1030 860 1190 1030 8600.5 1050 910 - - - 1090 950 780 1090 950 7800.6 940 - - - - - - 980 840 660 980 840 660