Manual 2100-590APage 6 of 67AIR CONDITIONING MODULE OPTIONSSTD = Standard equipment.1 CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break timer. On initialpower up, or any time the power is interrupted, the delay-on-make will be 2 minutes plus 10% of thedelay-on-break setting. There is no delay-on-make during routine operation of the unit. The modulealso provides the lockout feature (with 1 retry) for high and/or low pressure controls, and a 2-minutetimed bypass for low pressure control.2 HPC High pressure control is auto reset. Always used with compressor control module (CCM) which isincluded. See note 1.3 LPC Low pressure control is auto reset. Always used with compressor control module (CCM) which isincluded. See note 1.4 LAC Low ambient control permits cooling operation down to 0°F.5 SK CMC-15 is PTCR Start Kit can be used with all -A single phase models. Increases starting torque 2-3X. Not used for -B or -C 3-phase models. Do not use if SK111 is used.5 SK SK111 Start Capacitor and Potential Relay Start Kit can be used with all -A single phase models.Increases starting torque 9x. Not used for -B or -C 3-phase models. Do not use if CMC-15 is used.1MCC2CPH3CPL4CAL5KSdellatsnIyrotcaFedoCdellatsnIdleiFtraPDTS DTS DTS H 82-AMC ylnOdleiF 51-CMCro111KS