<6. Operation>48IM 01E25A01-01EN6. OperationAfter the installation of sensor into process piping, thewiring of input/output terminals, the configuration ofrequired parameters, and the zero adjustment prior toperation, the flowmeter outputs a flow signal from itsterminals as soon as the fluid is sent in the pipe.6.1 Pre-operation ZeroAdjustmentZero adjustment is carried out to ensure that the outputfor zero flow is 0% (i.e., 4 mA). Although adjustment tozero is performed at the manufacturing plant prior toshipment, this procedure must be carried out once againfollowing the installation of piping in order to match themagnetic flowmeter to its operating conditions.This section describes the zero adjustment procedureusing the display unit. For AXFA11, read the applicableuser’s manual as listed in Table 1.1.IMPORTANT• Zero adjustment should be carried out before actualoperation. Note that parameter setting or changecannot be carried out during execution of zeroadjustment (i.e., for approximately 30 seconds).• Zero adjustment should only be carried out whenthe sensor has been filled with measurement fluidand the fluid velocity is completely zero by closingthe valve.• Each time that the fluid being measured is changed,be sure to carry out zero adjustment with the newfluid.6.2 Zero Adjustment fromDisplay UnitA procedure of executing zero adjustment is as follows;Display Menu Path:Device setup ► Diag/Service ► Autozero ► ExecuteDevice setup ► Diag/Service ► Autozero ► Result ► Zero valueEnter the Setting Mode. (Read Section 5.3)F0601.aiDevice setupProcess variablesDiag/ServiceEasy setup wizard▲▼00 : 00SET SFT INC►►►Select “Diag/Service” accoriding to themenu path above.F0602.aiDiag/ServiceVerificationAutozeroAO/AI trim▲▼00 : 00SET SFT INC►►►Select “Autozero”.F0603.aiAutozeroExecuteResult▲▼00 : 00SET SFT INC►Select “Execute”.F0604.aiExecuteNot executeExecuteNot execute▲▼00 : 00SET SFT INCSelect “Execute”.F0605.aiExecuteExecute00 : 00SET SFT INCWhen “Execute” blinks, touch [SET] toexecute.F0606.aiAutozero functionexecuting...00 : 0000 : 08SET SFT INCThe time remaininguntil the end.Autozero starts, and the progress isdesplayed with a remaining time and abar graph. Wait for the completion.F0607.aiAutozeroExecuteResult▲▼00 : 00SET SFT INC►After Autozero finished, the displayreturns to “Autozero” menu.• Confirmation of zero adjustment resultF0608.aiResultZero value▲▼00 : 00SET SFT INCFor the result of Autozero, select “Result”and then “Zero value”.F0609.aiZero value– 00.018cm/s– 00.018cm/s– 99.999 + 99.99900 : 00SET SFT INCResult of Autozero is indicated as onthe left.NOTEWhen the zero adjustment result exceeds definedvalue, the warning [092: AZ wam] is indicated.Zero adjustment can be executed with the followingparameter.BRAIN Communication:B50:AUTOZERO EXEHART Communication Menu Path:Device root menu ► Basic setup ►Autozero ► Autozero ExeModbus Communication:Register Address: 40361