– 21 –Report Code ProgrammingAll report codes are entered using# 93 Menu Mode Programming, either throughReport Code Programming or through theZone Programming while entering other zone information. In the VISTA-32FB, reports are divided into six categories. Thesecategories represent the main menu options found inReport Code Programming. Reports and the categories in which theyare found are as follows:ALARM CODES RESTR, SUPV. CODES(for groups of 16 zones)SYSTEM GROUP #1Zone Alarm Reports Alarm RestoreTroubleTrouble RestoreBypassBypass RestoreClosing (Arm Away)Opening (Disarm)System Low BatteryLow Battery RestoreAC LossAC RestorePeriodic TestPowerCancelProgram TamperSYSTEM GROUP #2 SYSTEM GROUP #3 SYSTEM GROUP #4Arm STAYTime Set, Log ResetLog 50%, 90% FullEvent Log OverflowExit Error by ZoneExit Error by UserRecent CloseEarly OpenEarly CloseLate OpenLate CloseFailed to OpenFailed to CloseAuto-Arm FailedSchedule ChangeFire Walk-Test StartFire Walk-Test EndOff-NormalThe programming sequence that follows assumes that all reports for the system will be entered at one time. In actuality, it ispossible to skip from one main menu option to another by pressing 0 (NO) at each main menu option. Main menu options arehighlighted in bold text. To enter report codes, do the following:Enter Program Mode [Installer Code] + [8 0 0]. Then press #93. Enter 0 (NO) at each main menu option until the REPORTCODE PROG prompt is displayed.REPORT CODE PROG1 = YES 0 = NO 0Press 1 (YES) to enterReport Code Programming.Zone Alarm ReportsALARM, ID DIGIT?1 = YES 0 = NO 0Press 1 (YES) to enter Alarm Report Codes for zones. Press 0 (NO) to skip to the next mainmenu option.ENTER ZONE NO.000 = QUIT 001Enter the zone number for which you are entering the report code.Press [Q] to continue.001 REPORT CODE1st 00 2nd 00 000Enter the first digit of the Alarm report code (double-digit entry) and press [Q]. Enter the seconddigit of the Alarm Report Code.Press [Q] to continue.ENTER ZONE NO.000 = QUIT 001Enter the zone number for which the Report Code is being entered. When all zone Alarm Codeshave been programmed, enter 000 to Quit.Press [Q] to continue.QUIT REPORT MENU1 = YES 0 = NO 0If you have completely finished entering report codes, press 1 (YES) to quitReport CodeProgramming. If you wish to enter other system report codes, enter 0 (NO).Press [Q] to continue.www.PDF-Zoo.com