– 24 –Report Code ProgrammingAll report codes are entered using#93 Menu Mode Programming, either throughReport Code Programming, or throughZoneProgramming while entering other zone information. In the VISTA-128FBP/VISTA-250FBP, reports are divided into sixcategories. These categories represent the main menu options inReport Code Programming. Reports and the categories inwhich they are found are as follows:ALARM CODES RESTR, SUPV. CODES(for groups of 16 zones)SYSTEM GROUP #1Zone Alarm Reports Alarm RestoreTroubleTrouble RestoreBypassBypass RestoreClosing (arm AWAY)Opening (disarm)System Low BatteryLow Battery RestoreAC LossAC RestorePeriodic TestPowerCancelProgram TamperSYSTEM GROUP #2 SYSTEM GROUP #3 SYSTEM GROUP #4Arm STAYTime Set, Log ResetLog 50%, 90% FullEvent Log OverflowExit Error by ZoneExit Error by UserRecent CloseEarly OpenEarly CloseLate OpenLate CloseFailed to OpenFailed to CloseAuto-Arm FailedSchedule ChangeFire Walk-Test StartFire Walk-Test EndOff-NormalThe programming sequence that follows assumes that you will be entering all reports for the system at one time. In actuality,you may skip from one main menu option to another by pressing 0 (N) at each main menu option. Main menu options arehighlighted in bold text. To enter report codes, do the following:Enter Program Mode: [Installer Code] + 8 0 0 0. Then press #93. Enter 0 (N) at each main menu option until theReportCode Programming option is displayed.PROMPT EXPLANATIONREPORT CODE PROG1 = YES 0 = NO 0Press 1 (Y) to enter toReport Code Programming.Zone Alarm ReportsPROMPT EXPLANATIONALARM, ID DIGIT?1 = YES 0 = NO 0Press [1] (Y) to enter Alarm Report Codes for zones. Press [0] (N) to skip to the next main menu option.ENTER ZONE NO.000 = QUIT 001Enter the zone number for which you are entering the report code.Press [✱] to continue.001 REPORT CODE1st 00 2nd 00 00Enter the first digit of the Alarm report code (double-digit entry) and press [✱]. Enter the 2nd digit of theAlarm Report code.Press [✱] to continue.ENTER ZONE NO.000 = QUIT 001Enter the zone number for which you are entering the report code. When all zone Alarm Codes have beenprogrammed, enter 000 to Quit.Press [✱] to continue.QUIT REPORT MENU1 = YES 0 = NO 0If you have completely finished entering report codes, press [1] (Y) to quitReport Code Programming. If youwish to enter other system report codes, enter 0 (N).Press [✱] to continue.