Ferroresonant L-828/L-829 CCR Operation 2009 ADB Airfield Solutions, Incorporated 96A0288T 4-2All rights reserved Issued 9/04Table 4-1 Output Current from Rotary Switch (3-Step/6.6A)If you set the rotary switch tothe following...The result is...B10 4.8 A current outputB30 5.5 A current outputB100 6.6 A current outputTable 4-2 Output Current from Rotary Switch (5-Step/6.6 A)If you set the rotary switch tothe following...The result is...B1 2.8 A current outputB2 3.4 A current outputB3 4.1 A current outputB4 5.2 A current outputB5 6.6 A current outputTable 4-3 Output Current from Rotary Switch (5-Step/20 A)If you set the rotary switch tothe following...The result is...B1 8.5 A current outputB2 10.3 A current outputB3 12.4 A current outputB4 15.8 A current outputB5 20 A current outputSee Figure 4-1. Refer to Table 4-4 for instructions on how to set up and useremote control.Table 4-4 Remote ControlIf... Then...The rotary switch is set to positionREM and remote control wiring isconnected to remote controlterminal block TB1 on theregulatorRemote control of the regulator ispossible.The output current of the regulatorwill correspond to the brightnesssetting energized by remote 120 Vaccontrol signals.Switch is set to OFF Remote control signals will notoperate the regulator; that is, turnthe regulator on to a particularbrightness setting or turn theregulator off.No remote control connectionsexist on terminal block TB1(switch is set to REM)The position REM becomes anadditional OFF position; that is, theregulator is de-energized.Local Control (contd.)Remote Control