ABB | SACE Emax 2238 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A Electronic accessories | 14 - Ekip Link moduleContinued from the previous pageWith the Programmable Logic function, it is possible to program the activation of the Ekip Link up to 4 bits,each bit according to any combination of the status bits of a trip unit whose IP Address has been inserted.These four bits are indicated as states A, B, C and D remotely programmable, and their value is transmittedto the trip unit to which the Ekip Link module is connected.Exclusively with Ekip Dip trip units: the module can also be used with a function similar to that of the Ekip ComModbus TCP module, but only with the possibility to communicate with the ABB master (e.g.: Ekip Connect,or Ekip Control Panel).The following table shows the ports used by the module:Port Service Notes502/tcp Modbus TCP When the module is used as a Modbus TCP communication module.18/udp ABB proprietary In case of exchange of fast information between ABB devices.319/udp IEEE 1588 When IEEE protocol 1588 is enabled (see paragraph "Configuration",on page 241).320/udp68/udp DHCP Client DHCP Client enabled as an alternative to “Static Address = On”IMPORTANT: only one Ekip Link can be installed on each circuit-breaker.If connected to a withdrawable version of the circuit-breaker, the module allows the connected/disconnectedposition to be detected.IMPORTANT: when the circuit-breaker is in the disconnected position, the trip unitis disconnected from the module: in this condition, the only valid informationtransmitted is:• Connection of trip unit to Com module (Trip unit disconnected = disconnected).• CB position (CB isolated / CB connected = CB isolated).• Presence of com module ( = present; only valid for the module to which it is connected).Further details are given in document 1SDH001140r0001 (Communication SystemInterface for Emax 2), sections Status Global 1 [dlog], Status Accessories 1 andStatus Accessories 2.The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "16 - Otheraccessories" on page 244).Compatibility and power supply The module can be installed combined with Ekip Dip, Touch, Hi-Touch, G Touch, and G Hi-Touch trip units,and requires the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.