# Meaning Description1. No device communication No device physically connected OR message CRC error2. Wrong device connected The connected device Slave ID is NOT the right one3. Device not initialised The connected device has not been correctly initialised at theend of manufacturing (where applicable - see device dependent sections)4. Internal configuration map error Software configuration tables bug5. Wrong parameter number The requested parameter number doesn’t exist (only for writing operation)6. Wrong parameter value The parameter value is not allowed (only for writing operation)7. Command not executed The command is correctly received by the EP010 but it’s not possible tosend it to the device (e.g. the device is not connected).8. Watchdog fault Start-up diagnostics9. Modbus UART fault Start-up diagnostics10. RS 485 driver fault Start-up diagnosticsTable 5.Diagnostic codes6 Diagnostic & Troubleshooting6.1 DiagnosticThere are two different type of diagnostic information:1. local, by FAULT LED flashing2. remote, by diagnostic information available from FBPWhen the FAULT LED flashes at least one of the following conditions is verified6.2 TroubleshootingDepending on the status and behaviour of the LEDs it’s possible to get locally someinformation:# Symptom Diagnosis1. Some or all LEDs still ON after start-up sequence SW/HW bug2. - TX LED flashes (very fast) and No response from the device- FAULT LED flashes at 2 Hz and- FBP LED flashes at 2 Hz3. FAULT LED flashes at 2 Hz - Previously detected fault and- no communication with the FBPTable 6. TroubleshootingNOTE: the PWR LED is always ON if EP010 is powered.1SDH000509R0001 L3116EP010ABB SACE N° Pag.4/4EP010: INSTALLATION, USE AND DISINSTALLATION PROCEDURESINDEX FIGURES INDEXINSTALLATION INSTRUCTIONS ............ 1 Figure 1. Terminals, indicators and operatingelements on the front plate ............................. 1Figure 2. Dimensions for mounting ................. 21 DESCRIPTION .................................... 22 Replacement of a defective EP010 ...... 2 TABLES INDEX3 Mechanical data .................................. 2 Table 1. Modbus port terminals ...................... 14 Start-up ............................................... 3 Table 2. Device communication parameters ... 25 Run state ............................................. 3 Table 3. Start-up LEDs sequence ................... 36 Diagnostics & Troubleshooting ............ 4 Table 4. Normal LEDs behaviour .................... 36.1 Diagnostic .......................................... 4 Table 5. Diagnostic codes .............................. 46.2 Troubleshooting .................................. 4 Table 6. Troubleshooting ................................. 4Installation InstructionsThis document describes the installation, use and disinstallation procedures of EP010program further named as program.For more information see document. n.1SDH000510R0001.1 DescriptionFigure 1. Terminals, indicators and operating elements on the front plateTable 1. Modbus port terminalsTERMINAL NAME MODBUS CABLEL (left) A1 (right) B1SDH000509R0001 L3116EP010ABB SACE N° Pag.1/4Please note that NO communication between FBP and EP010 is active if thereis a failure on the relevant serial channel (UART).Total length of the Modbus cable from EP010 to connected device has tobe less or equal to 1 m.ProtectiveEarth