Endura AZ series integral and remote transmitterCombustion oxygen monitor 4 Electrical InstallationIM/AZ20E–EN Rev. F 174.5 Remote Transmitter – Remote AZ20 Probe Cable ConnectionsTerminalNumberTag ID Connection Type Cable Color Code1 H Heater Brown2 H Heater Blue3 SCN Screen Screens4 T / C – Thermocouple (–ve) White5 T / C+ Thermocouple (+ve) Green6 ACJC PT1000 Cold Junction Compensation Grey7 ACJC PT1000 Cold Junction Compensation Violet8 CELL – Oxygen Input (–ve) Black9 CELL + Oxygen Input (+ve) Red10 PS2 Pressure Switch – Gas 2 White / Yellow11 P COM Pressure Switch – Common White / Black12 PS1 Pressure Switch – Gas 1 White / Orange13 SV2 Solenoid Valve – Gas 2 White / Blue14 SV COM Solenoid Valve – Common White / Red15 SV1 Solenoid Valve – Gas 1 White / GreenTable 4.3 Remote Transmitter – Remote AZ20 Probe Cable ConnectionsFig. 4.6 Remote Transmitter – Remote AZ20 Probe Cable Connections To Probe –Refer to IM/AZ20P–EN forRemote Probe Connection DetailsAutoCal Connection (Terminals 10 to 15)StandardConnection(Terminals 1 to 9)