Technical data 171 Deratings for special settings in the drive control programEnabling special settings in the drive control program can require output currentderating.Ex motor, sine filter, low noiseContact ABB for the deratings of these cases:• drive is used with an ABB motor for explosive atmospheres (Ex) and EX motor inParameter 95.15 Special HW settings is enabled• sine filter given in the selection table on page 226 is used and ABB Sine filter inParameter 95.15 Special HW settings is enabled• Low noise optimization is selected in Parameter 97.09 Switching freq mode.Note: If Ex motors are used together with sine filters, EX motor in Parameter 95.15Special HW settings is disabled and ABB Sine filter in Parameter 95.15 Special HWsettings is enabled. Obey the instructions of the motor manufacturer.TypeACS880-11Output ratingsEX motor (ABB Ex motors) ABB Sine filterNominal use Light-dutyuseHeavy-duty useNominal use Light-dutyuseHeavy-dutyuseIN PN ILd IHd IN PN ILd IHdA kW A A A kW A AUN = 400 V09A4-3 10.0 4.0 9.5 8.0 9.2 4.0 8.7 7.212A6-3 12.9 5.5 12.0 10.0 12.1 5.5 11.5 9.2017A-3 17 8 16 12.6 16 7.5 15 12025A-3 25 11 24 17 24 11 23 16032A-3 32 15 30 25 31 15 29 23038A-3 38 19 36 32 37 18.5 35 31045A-3 45 22 43 38 43 22 41 36061A-3 61 30 58 45 58 30 55 43072A-3 72 37 68 61 64 30 61 58087A-3 87 45 83 72 77 37 73 64105A-3 105 55 100 87 105 55 100 87145A-3 145 75 138 105 145 75 138 105169A-3 169 90 161 145 169 90 161 145206A-3 206 110 196 169 206 110 196 169UN = 500 V07A6-5 7.6 4.0 7.2 5.2 7.0 3.0 6.7 4.811A0-5 11.0 5.5 10.4 7.6 10.2 4.0 9.7 7.0014A-5 14 7.5 13 11 13 5.5 12 10.2021A-5 21 11.0 19 14 19 7.5 18 13