126 Technical dataAmbient conditionsEnvironmental limits for the drive are given below. The drive is to be used in aheated, indoor, controlled environment.Operationinstalled for stationaryuseStoragein the protective packageTransportationin the protective packageInstallation site altitude 0 to 2000 m (6561 ft)above sea level. Foraltitudes over 2000 m,contact ABB.Output derated above1000 m (3281 ft). Seesection Output derating- -Air temperature -0 to +50 °C (32 to122 °F). No condensationallowed. Output deratedin the range +40 …+50 °C (+104 …+122 °F). See sectionOutput derating.-40 to +70 °C (-40 to+158 °F)-40 to +70 °C (-40 to+158 °F)Relative humidity 5 to 95% Max. 95% Max. 95%No condensation allowed. Maximum allowed relative humidity is 60% in thepresence of corrosive gases.Contamination IEC/EN 60721-3-3:2002:Classification ofenvironmental conditions-Part 3-3: Classification ofgroups of environmentalparameters and theirseverities - Stationaryuse of weather protectedlocationsIEC 60721-3-1:1997 IEC 60721-3-2:1997Chemical gases Class 3C2 Class 1C2 Class 2C2Solid particles Class 3S2. Noconductive dust allowed.Class 1S3. (packing mustsupport this, otherwise1S2)Class 2S2Atmospheric pressure 70 to 106 kPa0.7 to 1.05 atmospheres70 to 106 kPa0.7 to 1.05 atmospheres60 to 106 kPa0.6 to 1.05 atmospheresVibrationIEC 61800-5-1IEC 60068-2-6:2007,EN 60068-2-6:2008Environmental testing Part2: Tests –Test Fc: Vibration(sinusoidal)IEC/EN 60721-3-3:200210…57 Hz: max.0.075 mm amplitude57…150 Hz: 1 gIEC/EN 60721-3-1:199710…57 Hz: max.0.075 mmamplitude 57…150 Hz: 1gIEC/EN 60721-3-2:19972…9 Hz: max. 3.5 mmamplitude 9…20 Hz:10 m/s2 (32.8 ft/s2)ShockIEC 60068-2-27:2008,EN 60068-2-27:2009Environmental testing -Part 2-27: Tests - Test Eaand guidance: ShockNot allowed With packing max.100 m/s 2 (330 ft./s 2),11 msWith packing max.100 m/s2 (330 ft./s2),11 ms