218 ACS550 User’s ManualTechnical DataInput Power ConnectionsWarning! Do not operate the drive outside the nominal input line voltagerange. Over-voltage can result in permanent damage to the drive.Input Power SpecificationsDisconnect DeviceThe ACS550 does not include a disconnect device. A means to disconnect inputpower must be installed between the AC power source and the ACS550. Thisdisconnect device must:• Be sized to conform to applicable safety regulations, including, but not limited to,both national and local electrical codes.• Be locked in the open position during installation and maintenance work.The disconnect device must not be used to control the motor. Instead use the controlpanel, or commands to the I/O terminals for motor control.FusesBranch circuit protection must be provided by the end-user, and sized per nationaland local electric codes. The following tables provide fuse recommendations forshort circuit protection on the drive’s input power.Input Power (Mains) Connection SpecificationsVoltage (U1)208/220/230/240 VAC 3-phase (or 1-phase) +10% -15% forACS550-x1-xxxx-2.400/415/440/460/480 VAC 3-phase +10% -15% for ACS550-x1-xxxx-4.Prospective short-circuit current(IEC 629)Maximum allowed prospective short-circuit current in the supply is 100 kAin a second providing that the mains cable of the drive is protected withappropriate fuses. US: 100,000 AIC.Frequency 48…63 HzImbalance Max. ± 3% of nominal phase to phase input voltageFundamental powerfactor (cos phi1)0.98 (at nominal load)Cable TemperatureRating90 °C (194 °F) rating minimum.