Program features 121 DiagnosticsProgrammable analog outputOne programmable current output (0…20 mA) is available. Analog output signal canbe inverted, filtered and the maximum and minimum values can be adjusted. Theanalog output signals can be proportional to motor speed, output frequency, outputcurrent, motor torque, motor power, etc. The update cycle for the analog output is2 ms.It is also possible to write a value to an analog output through a serial communicationlink. Settings DiagnosticsActual signal Additional information0120, 0121 Analog input values1401 AI1/A2 signal lossAlarmAI1 LOSS / AI2 LOSS AI1/AI2 signal below AI1/AI2 FAULT LIMIT(3021/3022)FaultAI1 LOSS / AI2 LOSS AI1/AI2 signal below limit AI1/AI2 FAULT LIMIT(3021/3022)PAR AI SCALE Incorrect AI signal scaling (1302 < 1301 or 1305 <1304)Parameter Additional informationGroup 15 ANALOG OUTPUTS AO value selection and processingGroup 35 MOTOR TEMP MEAS AO in motor temperature measurementActual signal Additional information0124 AO valueFaultPAR AO SCALE Incorrect AO signal scaling (1503 < 1502)Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com