LMDX-100Digital Lighting ManagementDual Technology Corner MountOccupancy SensorSensor30'30'SENSOR PLACEMENTSensorCeilingCOVERAGE PATTERNCoverages shown are maximum andrepresent half-step walking motion.Side view10’Top view40’0 7’ 15’ 25’ 45’PIRcoverage45ft.Ultrasoniccoverage28ft.Quick Start GuideLineVoltageRoomControllerJ-BoxesDaylight SensorSwitchSwitchCorner MountSensor Ceiling MountSensor DLM Local NetworkLow VoltageLMRJ CablesLoads21Line/HotBlack wireNeutralWhite wireRed wireto Load A (1)Yellow wireto Load B (2)LMRC102RoomControllerJ BoxCorner MountOccupancySensorSwitchToLoad/Line(Class 1 wiring)DLM Local Network(low voltage, Class 2)LMRJ CablesVoltage: ............................................................................... 24VDCCurrent Consumption: ......................................................... 20mAPower Supply: ............. Watt Stopper/Legrand Room ControllersConnection to the DLM Local Network .......................RJ-45 plugDLM Local Network Characteristics:Provides low voltage power over Cat 5e cable (LMRJ).Supports up to 24 communicating devices, including 4LMRC-10x or LMPL-101 max per each DLM Local Network.Free topology up to 1,000ft of low voltage cable.Environment ................................................. For Indoor Use OnlyOperating Temperature ....................32° to 131°F (0° to 55°C)Storage Temperature ...................... 23° to 176°F (-5° to 80°C)Relative Humidity ...........................5 to 95% (non condensing)Patent PendingTHIS UNIT IS PRE-SET FOR PLUG n’ GOOPERATION, ADJUSTMENT IS OPTIONAL.For full operational details, adjustment and morefeatures of the product, see the DLM SystemInstallation Guide provided with the LMRC-102 andalso available at www.wattstopper.comCONNECTIVITYThe illustrations below show examples of free-topology wiring. The LMDX-100communicates to all other Digital Lighting Management devices connected to the lowvoltage DLM Local Network, regardless of their position on the DLM Local Network.INSTALLATION SHALL BEIN ACCORDANCE WITH ALLAPPLICABLE REGULATIONS,LOCAL AND NEC CODES.Intended for Listed Class2 DLM Devices.For Class 2 DLM devices -To be connected to a Class2 power source only.For Class 2 Device Wiring Only –Do Not Reclassify and Install asClass 1, or Power and LightingWiring.Wire connections shall be ratedsuitable for the wire size (leadand building wiring) employed.