Quick Start GuideSENSOR PLACEMENT (10’ MAX. HEIGHT)CONNECTIVITYThe illustrations below show examples of free-topology wiring. The LMDC-100 communicates to all other Digital LightingManagement devices connected to the low voltage DLM Local Network, regardless of their position on the DLM Local Network.LMDC-100Digital Lighting ManagementDual Technology Ceiling MountOccupancy SensorSensor25'25' Strong airsupply6’SensorMount sensor at least 6’ away from air supply.Avoid obstacles that block sensor’s line-of-sight.PendantfixtureLineVoltageRoomControllerJ-BoxesDaylight SensorSwitchSwitchCorner MountSensorCeiling MountSensor DLM Local NetworkLow VoltageLMRJ CablesLoads21Line/HotBlack wireNeutralWhite wireRed wireto Load A (1)Yellow wireto Load B (2)LMRC102RoomControllerJ BoxCeiling MountOccupancySensorSwitchToLoadVoltage: .....................................................................................24VDCCurrent Consumption: ...............................................................20mAPower Supply: ................... Watt Stopper/Legrand Room ControllersConnection to the DLM Local Network ........................ 2 RJ-45 portsDLM Local Network Characteristics:Provides low voltage power over Cat 5e cable (LMRJ).Supports up to 24 communicating devices, including 4LMRC-10x or LMPL-101 max per each DLM Local NetworkFree topology up to 1,000ft of low voltage cable.Environment .......................................................For Indoor Use OnlyOperating Temperature ................. 32° to 131°F (0° to 55°C)Storage Temperature ....................23° to 176°F (-5° to 80°C)Relative Humidity ........................ 5 to 95% (non condensing)Patent PendingTHIS UNIT IS PRE-SET FOR PLUG N’ GO™OPERATION, ADJUSTMENT IS OPTIONAL.For full operational details, adjustment and morefeatures of the product, see the DLM System InstallationGuide supplied with the LMRC-102 and also available atwww.wattstopper.comINSTALLATION SHALL BEIN ACCORDANCE WITH ALLAPPLICABLE REGULATIONS,LOCAL AND NEC CODES.Intended for Listed Class 2 DLMDevices.For Class 2 DLM devices -To be connected to a Class 2power source only.For Class 2 Device Wiring Only –Do Not Reclassify and Install asClass 1, or Power and LightingWiring.Wire connections shall be ratedsuitable for the wire size (leadand building wiring) employed.25 ft(7.62m)25 ft x 25 ft(7.62m x 7.62m)COVERAGE PATTERNThe LMDC-100 provides a 360° coverage pattern.Thecoverage shown represents maximum coverage forwalking motion at a mounting height of 10 feet.PIRCoverageUltrasonicCoverage