9Recycle: The packing material is recycled, please reserve packingmaterial for using in the future.2.2 Wiring TableNote:The diameter of connection wire depend on rated power ofUPSIn the below table, for single phase model, “L” represents line wire, forthree phase model, “L” represents the wire of L1,L2,L3 and the diameterof three phase is the same.Model EX6K EX6KL EX10K EX10KL EX3110KL EX3115KL EX3120KLInputG 10AWG6m㎡10AWG6m㎡8AWG10m㎡8AWG10m㎡8AWG10m㎡6AWG25m㎡6AWG25m㎡N 10AWG6m㎡10AWG6m㎡8AWG10m㎡8AWG10m㎡8AWG10m㎡6AWG25m㎡6AWG25m㎡L 10AWG6m㎡10AWG6m㎡8AWG10m㎡8AWG10m㎡8AWG10m㎡6AWG25m㎡6AWG25m㎡Battery+ 10AWG6m㎡10AWG6m㎡8AWG10m㎡8AWG10m㎡8AWG10m㎡6AWG25m㎡6AWG25m㎡- 10AWG6m㎡10AWG6m㎡8AWG10m㎡8AWG10m㎡8AWG10m㎡6AWG25m㎡6AWG25m㎡G 10AWG6m㎡10AWG6m㎡8AWG10m㎡8AWG10m㎡8AWG10m㎡6AWG25m㎡6AWG25m㎡OutputL 10AWG6m㎡10AWG6m㎡8AWG10m㎡8AWG10m㎡8AWG10m㎡6AWG25m㎡6AWG25m㎡N 10AWG6m㎡10AWG6m㎡8AWG10m㎡8AWG10m㎡8AWG10m㎡6AWG25m㎡6AWG25m㎡G 10AWG6m㎡10AWG6m㎡8AWG10m㎡8AWG10m㎡8AWG10m㎡6AWG25m㎡6AWG25m㎡2.3 UPS ConnectionDangerous: The rated current of mains breaker installed by user must bigger thaninput current of UPS, or the mains breaker may be damaged.(About maximum input