PREMIER AD INSTALLATION MANUAL. Software:31/3/04 & LC6Approved Document No: GLT.MAN-105 PAGE 15Issue : 1.02 Authorised: GH Date: 15/03/20046. Select Option 3 (Configure). The panel will sayConfiguration in progress please wait.This takes around 20 seconds.7. To check that the panel has read all the devices onloop 1, select option 1 Lp1 Dev. If the loop contentsare as expected, go to point 8, otherwise go toLoop Contents Fault Finding on page 16.8. Select cancel to leave this menu & selectoption 2 (Lp2 Dev). If the loop contents are asexpected, go to point 9, otherwise go toLoop Contents Fault Finding on page 16.9. Press cancel to leave the menu. The panel is now configured, and will function as abasic system, (press 6 for covered), but it is more useful to enter device labels, to give amore precise location of an alarm device. We recommend that the device labels beentered to allow the panel to be more user friendly during normal operation.10. Select option 4 for message editing. The panelwill now ask for its write enable switch to be set tothe on position . (This is the dip switch on the CPUboard, switch 1).11. The panel will now ask for the loop number, andthe loop address of device name to be entered. Pressenter to confirm loop 1, and enter again to confirmaddress 001. Enter the device label using the built inkeyboard. The label can be 20 characters long,so try to be as descriptive as possible. Use the capslock for capital letters. The delete button is used tocorrect mistakes. When the label has been entered,record the device type & label in the system setupchart in the user manual. Press enter 3 times to move to the next device (or enter the loopnumber and address to move forward several places.12 when all devices have been entered, press Cancelto exit the message editing screen. The panel will askfor the write enable switch to be set back to the offposition .NOTE: IF THE PANEL IS POWERED DOWN WITH THE WRITE ENABLE SWITCH ON,IT WILL ERASE THE DEVICE LABELS WHEN IT IS RE-POWERED.The panel is now configured and ready for operation.Configuration inProgressPlease WaitCO 00 SCC 14 Loop 1I/O 01 ION 00 DAD 00ZMU 00 OPT 45 CancelHET 03 BGU 05 = ExitCO 00 SCC 14 Loop 2I/O 01 ION 00 DAD 00ZMU 00 OPT 45 CancelHET 03 BGU 05 = ExitMessage EditingLoop:1 Address:001Floor 1. Bedroom 20Can: Exit Ent: NextPlease Set TheWrite Enable SwitchTo the On PositionPlease Set TheWrite Enable SwitchTo the Off Position