INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.NApproved Document No: GLT-211-7-1Issue 1.9 Author: MG/NJ Date: 06/04/2016 PAGE 3015 VIEWING PANEL INFORMATION15.1 Menu StructureTo help locate the different features available, the menu structure of the ID2 panel is shown here.MENU LAYOUTMAIN MENU SUB MENU 1 SUB MENU 2 DESCRIPTIONCONFIGURATION MENU 1 – THE USER MENU1:Clock - - Set the date and time2:Logs VIEW EVENT LOG1: Alarms - View all fire alarm events2: Faults - View all fault events3: System - View all other events (eg User access, menuaccess, clock change, etc)4: All - View all events3:Devices - - View device type and zone / ID information aswell as any text labels4: Engineer - - Puts the panel into Engineer menu 1ENGINEER MENU 1 – THE ENGINEER MENU1:Zones 1. ZoneSummary- View the zones and shows how many devicesare fitted to each zone2. ConfigureNowConfigure the Zones2:Panel/Zone Text - - Set Panel Name and Zone Label3:ID Device - - * Edit device label (Press ENTER)* Turn on alarm LED / Flasher (Press 4)* Ring sounder(Press GENERAL TEST)* Select alarm verification(Press 8)* Configure Sandwich Sounder Base (Press 7)* Disable this device.(Press General Disable)* Configure I/O OUTPUT(Press 8)* Configure I/O INPUT (Press 6)ENGINEER MENU 24:Alarm Verify 1:Verify Time - Detector verify time (1:00 – 3:45)2:ChooseDevices- Select the device that requires verification (thiscan only be set to a smoke detector)5:Config Alarms 1:Relay - Edit the way the fire relay works in an alarmcondition (Common, Manual, Detector)2:Interfaces - Edit the Interfaces work in an alarm condition(Common, Zonal detector, Zonal all, own input,panel link, Manual alarm, Detector alarm, ZonalMCP)3:Alarm Tone - Change the sounder output tone (there are 16different tones)4.Resound Sets whether sounder operate for any newalarm, an alarm from a new zone, or only for thefirst alarm. (EN54 Requirement)6:Misc 1:Language Select the panel language (there are 5)2:Version Shows the panel and loop software version3:Topology Changes the panel from Radial wiring to LoopWiring6:Reset Reset the event log and restore back to factorydefault settings (Requires the code 159)