TR1200 12320-0702-03 Seite 20 / 20 www.ziehl.de15 Appendix SIPROTEC configurationThe sensor connections and the configuration of the TR1200 for evaluation on a Siemens SIPROTECprotection device are described below. While doing so, the Thermo box operation mode is differentiated.6 RTD Simplex operation mode (1x TR1200 works like 1x TR600) = Factory setting Connect Sensors 1…6 Configure Sensors 1...6 in menu item 8SEN.8 depending on the connection(configure sensors that are not connected as "nc") Configure Sensors 7…12 in menu item 8SEN.8 as "nc" Set device address in menu item 8bus.8 8adr8 to 0The TR1200 transmits the data from Sensors 1...6 cyclically every 3s.6 RTD half duplex operation mode(1x TR1200 works like 1x TR600) Connect Sensors 1…6 Configure Sensors 1...6 in menu item 8SEN.8 depending on the connection(configure sensors that are not connected as "nc") Configure Sensors 7…12 in menu item 8SEN.8 as "nc" Set device address in menu item 8bus.8 8adr8 to 1The TR1200 transmits the data from Sensor 1…6 on request with address 1.12 RTD half duplex operation mode (1x TR1200 works like 2x TR600) Connect Sensors 1…12 Configure Sensors 1...12 in menu item 8SEN.8 depending on the connection(configure sensors that are not connected as "nc") Set device address in menu item 8bus.8 8adr8 to 1The TR1200 transmits the data from Sensors 1...6 on request with address 1,and from Sensors 7...12 on request with address 2.