5.2 Hardware configurationn The description here refers to modules that are at the same bus together with theCPU. In order to address the installed modules individually, specific addresses in theCPU have to be assigned to them. The allocation of addresses and the configurationof the installed modules is a function of the Siemens SIMATIC manager.n Here navigate within the hardware catalog to the according CP and place it at theS7-300 station.1. Start the Siemens SIMATIC Manager.2. Swap to the hardware configurator.3. Place a profile rail via drag&drop from the hardware catalog to the project window.4. Project the CPU and the corresponding modules.Place the corresponding modules via drag&drop from the hardware catalog to thecorresponding slot of the profile rail.5. To project the VIPA CP 341-1CH01 the Siemens CP 341 (6ES7 341-1CH01-0AE0)at the according slot is to be used.6. Adjust via the CP "properties" the transmission protocol and the protocol specificparameters (see protocol parameters). Note the address from which the CP isembedded. This value is necessary for the integration in your user program.Ä Chap. 5.3 ‘Communication with the user program’ page 317. Save and translate your project and transfer it to the CPU.OverviewProject engineeringVIPA System 300SDeploymentHardware configurationHB130 | CP | 341-1CH01 | en | 18-4028