Commissioning vacon • 2324-hour support +358 (0)40 837 1150 • Email: fieldbus@vacon.com 14. COMMISSIONINGThe Vacon Ethernet board is commissioned with the control keypad by giving values to appropriateparameters in menu M7 (or with NCIPConfig tool, read chapter IP Tool NCIPConfig). Keypad com-missioning is only possible with NXS and NXP series AC drives. AC drives of the NXL series can onlybe commissioned with the NCIPConfig tool.4.1. Expander board menu (M7)TheExpander board menu makes it possible for the user to see which expander boards are con-nected to the control board and to reach and edit the parameters associated with the expanderboard.Enter the following menu level (G#) with theMenu button right. At this level, you can browse troughslots A to E with theBrowser buttons to see what expander boards are connected. On the lowermostline of the display you see the number of parameter groups associated with the board. If you stillpress theMenu button right once you will reach the parameter group level where there are onegroup in the Ethernet board case: Parameters. A further press on theMenu button right takes you toParameter group.4.2. Profinet parameters# Name Default Range Description1 Comm. Timeout 10 0…255 s2 IP Part 1 192 1…223 IP Address Part 13 IP Part 2 168 0…255 IP Address Part 24 IP Part 3 0 0…255 IP Address Part 35 IP Part 4 10 0…255 IP Address Part 46 SubNet Part 1 255 0…255 Subnet Mask Part 17 SubNet Part 2 255 0…255 Subnet Mask Part 28 SubNet Part 3 0 0…255 Subnet Mask Part 39 SubNet Part 4 0 0…255 Subnet Mask Part 410 DefGW Part 1 192 0…255 Default Gateway Part 111 DefGW Part 2 168 0…255 Default Gateway Part 212 DefGW Part 3 0 0…255 Default Gateway Part 313 DefGW Part 4 1 0…255 Default Gateway Part 414 InputAssembly - -NOT USED in Profinet15 OutputAssembly - -NOT USED in ProfinetTable 2. Ethernet parameters4.3. IP AddressIP is divided into 4 parts. (Part = Octet) Default IP Address is 192.168.0.10.Communication timeoutDefines how much time can pass from the last received message from the Master Device beforefieldbus fault is generated. Communication timeout is disabled when given the value 0. The commu-nication timeout value can be changed from the keypad or with NCIPConfig tool (see chapter IP ToolNCIPConfig).