6vacon • 34 CommunicationsLocal contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/Process Data Master -> Slave (max 22 bytes)Control word bitsFor control word bit descriptions, see Chapter 10. APPENDIX 2 - CONTROL AND STATUS WORD.6.3.7 FB Process data OUTProcess Data Slave -> Master (max 22 bytes)Table 21. Fieldbus Process Data INAddress Name Range/Type16-bit **. In VACON® 100 family AC drives, the Control Word and the Status Word areformed of 32 bits. Only the initial 16 bits can be read in the 16-bit area.32-bit2001 2051 = High data2052 = Low data FB Control Word Binary coded2002 - FB General Control Word Binary coded2003 2053 = High data2054 = Low data FB Speed Reference 0…10000 (100%)2004 2055 = High data2056 = Low data FB Process Data In 1See Chapter 9.APPENDIX 1 -PROCESS DATA2005 2057 = High data2058 = Low data FB Process Data In 22006 2059 = High data2060 = Low data FB Process Data In 32007 2061 = High data2062 = Low data FB Process Data In 42008 2063 = High data2064 = Low data FB Process Data In 52009 2065 = High data2066 = Low data FB Process Data In 62010 2067 = High data2068 = Low data FB Process Data In 72011 2069 = High data2070 = Low data FB Process Data In 8Table 22. Fieldbus Process Data OutAddress Name Range/Type16-bit 32-bit2101 2151 = High data2152 = Low data FB Status Word Binary coded2102 - In case of 16-bit, FB GeneralStatus Word (High data) Binary coded2103 2153 = High data2154 = Low data FB Actual Speed 0…10000(100.00%)