40Version 1.0 / 11-2018ТМ7.0 CoolING UNItThe cooling unit performance control is executed by scanning 3 tempera-ture sensors:- Sensor No.1 - is located in the lower part of the product dispensing tray;- Sensor No.2 - is located in the upper part of the product dispensing tray;- Sensor No.3 - is located on the cooling unit evaporator (fig. 7.1).Notice:Recommended temperature settings:- Min. temperature 4±2°С- Max. temperature 10±2°С- Min. evaporator temperature 1 ± 1°С- Max. evaporator temperature 5 ± 1°С12figure 7.1 - location of temperature sensor No. 31 - Temperature sensors2 - BucklesAttENtIoN!To maintain the correct operating mode of the cooling unit, it’s impor-tant that the temperature sensor No. 3 is installed correctly. It shouldbe securely fixed on the next to last evaporator elbow as shown infig. 7.1. The sensor installation should be executed outside the vend-ing machine. After placing the cooling unit inside the vending ma-chine the sensor connector should be connected to the temperaturesensor wiring harness.