10.2 Batch Uploading from Controller6F8C1067 4110(4) RAS information readRequest to read FL312 RAS information (internal error information and event log) fromS controller.CMD DATAF 0 F 0+0 4 +0 Read data length+1 type Read RAS information+2 Start position+3 Read count+4 data area lengthNote1: Read data length: Byte length of read RAS informationData area length: Byte length of data sectionType: 1 RAS counter2 Specification prohibited3 Port information4 Event trace5 FA section information6 UDP stack information7 RAS information clear (for 1, 3, 4)(Completion status error occurs if any other type is specified)Start position: Event trace read start position (valid only when type=4)Read count: Event trace read count (valid only when type=4)The completion status (see appendix) of this request is stored in STATUS ofXMIT_T.See "Appendix RAS Information" for the RAS information contents.Figure 10-4 RAS information read request(5) Reset requestRequest to reset the FL312 module. FL312 initializes itself when it receives thisrequest. If initialized, no response is returned from FL312 for this request. FL312returns a response if this request cannot be accepted due to error.When initialization completes, FL312 enters standby mode and waits for parameters.This request takes approximately 2 seconds to complete normally. S controller mustverify that reset request was executed as follows.• Node status initialize bit changes to "0" and standby bit changes to "1".CMD DATAF 0 F 0+0 5 +0 NoneNote1: The completion status (see appendix) of this request is stored in STATUS ofXMIT_T.Figure 10-5 Reset request