13-1 13. Trip information and measuresIIIIII123456789101112131415161718If a trip occurs, make failure diagnosis according to the table below before contacting your Toshiba dis-tributor.■ Term description■ Trip information13 Trip information and measures13. 1 Description of trip and alarm informationand measuresTripOutput of the inverter is turned OFF for protection of the inverter or external equipment.A failure signal can be output if the output terminal function is assigned.(A failure signal is assigned to the terminal [FL] in the default setting).AlarmIndicates a condition that the inverter or external equipment may be damaged if continued.A signal can be output if the output terminal function is assigned.Under voltage, etc. are displayed with blinking on the operation panel.Pre-alarmA condition close to the trip level.A signal can be output when the output terminal function is assigned."C", "P", "L", and "H" blink in the operation panel during run for overcurrent, overvoltage,overload, and overheat respectively.Message Informs a status of the inverter and setting error. It is not an alarm.TripdisplayFailurecode Trip name Detection factor MeasuresE 0011 EmergencyoffEmergency off is input.1) When a run command is other than theoperation panel, [STOP/RESET] keywas pressed twice.2) A signal was input to the input terminalin which emergency off is assigned.3) Emergency off is input fromcommunication.• Reset after solving problems.• Clear the emergency off signal.E-11 002B Brake answererror *The system does not reply even after thesetting time in time> elapsed.• Check the system.• Check if the setting is correct.When not used, set ="0.0: Dis-abled".E-12 002C PG error 1) PG is disconnected.2) Error exists in PG wiring.3) PG voltage is improper.• Check the PG wiring.• Check if the PG settings are correct.,*Enable/Disable can be selected for trip with a parameter.