6DN code ConfigurationConnect a remote controller and set the DN codes as required. To access theDN codes Press the Test Set and Cl. You can then press the temperature upand down arrows to select the code to be modified. Once the selected codehas been updated press the SET button to register the change and then theSpanner button to exit.THESE CONFIGERATION CODES MUST BE SETFAILURE TO DO THIS COULD RESULT IN BUILDING DAMAGESet DN Code 67 to the required on temperature.Table 1Set DN Code 68 to the required heater operation time.Table 2Set DN Code 69 to the required heater run on time. When switched off on the remotecontrollerTable 3Heater OperationWhen the unit air on sensor in the unit reaches the value set in (Table 1) the heaterwill be enabled. The heater will operate for the time set in (Table 2) at the end of thistime the heater will switch off . If the unit air on value is still below the set value inTable 1 the process stars again. if it is above the heater remains OFF. Should thetemperature significantly rise the heater will turn off. If the unit is switched of f on theremote controller the fan will run on for the time set in table 3