– 73 –FILE NO. SVM-130108-1-6. Monitor Function of Remote Controller SwitchCalling of sensor temperature displayEach data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitormode from the remote controller.3 Push UNIT LOUVER (left side button) button to select the indoor unit to be monitored.Each data of the indoor unit and its outdoor units can be monitored.4 Pushing TESTbutton returns the status to the usual display.∗1 The indoor discharge temperature of CODE No. [F8] is the estimated value from TC or TCJ sensor.Use this value to check discharge temperature at test run.(A discharge temperature sensor is not provided to this model.)• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.• If the combined outdoor unit is one before 2 or 3 series, the outdoor unit data [6D], [70], [72] and [73]are not displayed.1 Push TEST+ CLbuttons simultaneously for 4 seconds tocall the service monitor mode.The service monitor goes on, the master indoor unit No. isdisplayed at first and then the temperature of CODE No. isdisplayed.2 Push temperature set TEMP. buttons and then changethe CODE No. of data to be monitored.The CODE No. list is shown below.1 2 3 4Returned to usual display2 4 1 3SETTIMETIMER SETTESTFILTERRESETTEMP.CLFANSAVESWING/FIXVENTMODEON / OFFUNIT LOUVERIndoor unit dataCODE No.0102030407F2F3F8Data nameRoom temperature(Remote controller)Indoor suction temperature (TA)Indoor heat exchanger (Coil)temperature (TCJ)Indoor heat exchanger (Coil)temperature (TC)Indoor fan revolution frequencyIndoor fan calculated operation timeFilter sign timeIndoor discharge temperature*1Unit°C°C°C°Crpm×100h×1h°COutdoor unit dataCODE No.60616263656A6D707273F1Data nameOutdoor heat exchanger (Coil) temperature (TE)Outside temperature (TO)Compressor discharge temperature (TD)Compressor suction temperature (TS)Heat sink temperature (THS)Operation current (× 1/10)Outdoor heat exchanger (Coil) temperature (TL)Compressor operation frequencyOutdoor fan revolution frequency (Lower)Outdoor fan revolution frequency (Upper)Compressor calculated operation timeUnit°C°C°C°C°CA°Crpsrpmrpm×100hSVM-13010_051-106.indd 73SVM-13010_051-106.indd 73 2/1/13 2:49 PM2/1/13 2:49 PM PreviousNext |