– 69 –FILE NO. SVM-13010∗ The swing mode selection (DN code No. [F0]), louver fix (DN code No. [F1] to [F4]) and restriction ratio setting forsave operation (DN code No. [C2]) can be set/changed from the normal DN setup (Detail DN setup).DN4245C2CCCDD0D1D3D4F0F1F2F3F4ItemSelf-clean operation timeSelection of louver horizontal dischargepositionCurrent demand X% to outdoor unitSetting of self-clean operation forced stopClean operation stop function when[ON/OFF] operation is prohibited.Existence of remote controller save functionExistence of 8°C heating operation functionRevolution frequency of self clean operationDisplay / No display of[Dry operation] during self clean operationLouver swing modeLouver No.1 fixed positionLouver No.2 fixed positionLouver No.3 fixed positionLouver No.4 fixed positionContentsh0:210.0oth5.0:0000enoN:0000Set when compressor-ON time is 10 to 60 minutes.When ON-time is 60 minutes or more,the double of this operation time setting is set.0000: Smudging-less setting0002: Cold draft preventive setting0050: 50% to 0100: 100%0000: No• Clean operation is performed in case of stop by HA input.• HA operation output OFF during clean operation in case ofstop by remote controller0001: Yes• Clean operation is not performed in case of stop by HA input.• HA operation output ON during clean operation in case of stopby remote controllerThe air conditioner stops (including fire alarm such as remotemonitor system) while setup of [ON/OFF] operation prohibited(Central 1, 2) is performed from the central controller side.0000: Valid (Clean operation)0001: Invalid (No clean operation)0000: Invalid (Impossible) 0001: Valid (Possible)0000: Invalid (Impossible) 0001: Valid (Possible)0000: Invalid (Self clean operation is not carried out.)0001: Valid (Self clean operation is practiced with 210 rpm.)0000: Display 0001: No display0000: No synchronization 0001: 4-way synchronizationelcyC:3000lauD:20000000: Release (Free)0001 to 0005: Horizontal discharge position toDownward discharge position0000: Release (Free)0001 to 0005: Horizontal discharge position toDownward discharge position0000: Release (Free)0001 to 0005: Horizontal discharge position toDownward discharge position0000: Release (Free)0001 to 0005: Horizontal discharge position toDownward discharge positionAt shipment from factory0002: 1 hour0000: Smudging-less setting0075: 75%0000: None0000: Valid0001: Valid (Possible)0001: Valid (Possible)0001: Valid(210 rpm / operation)0000: Display0001: 4-waysynchronization0000: Release0000: Release0000: Release0000: Release