– 75 –8-1-6. Monitor Function of Remote Controller Calling of sensor temperature displayEach sensor temperature of the remote controller, indoor unit, and outdoor unit can become known bycalling the service monitor mode from the remote controller.1 Push TEST+ CLbuttons simultaneously for 4 seconds tocall the service monitor mode.The service monitor goes on, the master indoor unit No. isdisplayed, at first and then the temperature of CODE No.0000000000 isdisplayed.2 Push temperature set TEMP. buttons and then changethe CODE No. of data to be monitored.The item code list is shown below:1 2 3 4Returned to usual display2 4 1 3SETTIMETIMER SETTESTFILTERLLRESETTEMP.CLFANSAVEAASWING/FIXVENTMODEON / OFFUNIT LOUVERTØ3 Push UNIT LOUVERbutton to select the indoor unit to be monitored.Each data of the indoor unit and its outdoor units can be monitored.Ø4 Pushing TESTbutton returns the status to the usual display.• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.• If the combined outdoor unit is one before 2 or 3 series, the outdoor unit data [6D], [70], [72] and [73] arenot displayed.Indoor unit dataCODE No.0102030407F2F3F8Data nameRoom temperature(Remote controller)Indoor suction temperature (TA)Indoor heat exchanger (Coil)temperature (TCJ)Indoor heat exchanger (Coil)temperature (TC)Indoor fan revolution frequencyIndoor fan calculated operation timeFilter sign timeIndoor discharge temperatureUnit°C°C°C°Crpm×100h×1h°COutdoor unit dataCODE No.60616263656A6D707273F1Data nameOutdoor heat exchanger (Coil) temperature (TE)Outside temperature (TO)Compressor discharge temperature (TD)Compressor suction temperature (TS)Heat sink temperature (THS)Operation current (× 1/10)Outdoor heat exchanger (Coil) temperature (TL)Compressor operation frequencyOutdoor fan revolution frequency (Lower)Outdoor fan revolution frequency (Upper)Compressor calculated operation timeUnit°C°C°C°C°CA°Crpsrpmrpm×100hAMP Air Conditioningwww.ampair.co.uk | sales@ampair.co.uk PreviousNext |