E6581611D-1444.5 EASY key functionpsel : EASY key mode selectionf750 : EASY key function selectionf751 to f782 : Easy setting mode parameter 1 to 32[Parameter setting]Title Function Adjustment range Default settingpsel EASY key mode selection0: Standard setting mode at power on1: Easy setting mode at power on2: Easy setting mode only 0f750 EASY key function selection0: Easy / standard setting mode switching function1: Shortcut key2: Local / remote key3: Monitor peak / minimum hold trigger0 Easy / Standard setting mode switching function (f750=0): Default settingIt is possible to switch between standard mode and easy setting mode when you push the EASY key while theinverter is stopping.Standard setting mode is selected when the power is turned on at default setting.The way parameters are read out and displayed varies according to the mode selected.Easy setting modeAllows pre-registration (easy setting mode parameters) of frequently changed parameters and reading of onlyregistered parameters (maximum of 32 types).In the Easy setting mode, the EASY key lamp lights.Standard setting modeStandard setting mode in which all parameters are read out.[How to read out parameters]Use the EASY key to change between Easy setting mode and Standard setting mode, and then press the MODEkey to enter the setting monitor mode.Turn the setting dial to read the parameter.The relation between the parameter and the mode selected is shown below.• FunctionIt is possible to switch between standard mode and easy setting mode using the EASY key. (default setting)Up to 32 arbitrary parameters can be registered to easy setting mode.The EASY key can select following four functions.• Easy / Standard setting mode switching function• Shortcut key function• Local / Remote switching function• Peak hold function