MBS (Wallmount) Installation - 64523-0091Maintenance Bypass Switch - Wall-Mount CabinetDead FrontKeyedMechanicalInterlockTop Access PanelBottom Access PanelLifting EyesDead FrontLockableFrontPanelDoorMBS - Door Closed MBS - Door OpenLOTO(Lock out/Tag out)HaspMBS BREAKER OPTIONS (All cabinets are ANSI-61 Gray (Munsell No. 8.3G 6.10/0.54.))Part Number* Dim. W x D x H (in) Wt (lb) UPS kVA Voltage Breaker Size Withstand kAICMBSWH-150-F3-KK 30.1 x 10.8 x 42.1 130 15 208/120V 60A 65,000MBSWH-250-F3-KK 30.1 x 10.8 x 42.1 130 25 208/120V 100A 65,000MBSWH-300-F3-KK 30.1 x 10.8 x 42.1 130 30 208/120V 125A 65,000MBSWH-500-F3-KK 30.1 x 10.8 x 42.1 130 50 208/120V 200A 65,000MBSWH-800-F3-KK 36 x 12.8 x 48.1 280 80 208/120V 300A 65,000MBSWH-10K-F3-KK 36 x 12.8 x 48.1 385 100 208/120V 400A 65,000MBSWH-150-S3-KK 30.1 x 10.8 x 42.1 130 15 480V 40A 35,000MBSWH-250-S3-KK 30.1 x 10.8 x 42.1 130 25 480V 40A 35,000MBSWH-300-S3-KK 30.1 x 10.8 x 42.1 130 30 480V 50A 35,000MBSWH-500-S3-KK 30.1 x 10.8 x 42.1 130 50 480V 100A 35,000MBSWH-800-S3-KK 30.1 x 10.8 x 42.1 130 80 480V 125A 35,000MBSWH-10K-S3-KK 30.1 x 10.8 x 42.1 130 100 480V 175A 35,000MBSWH-12K-S3-KK 30.1 x 10.8 x 42.1 130 125 480V 200A 35,000MBSWH-15K-S3-KK 30.1 x 10.8 x 42.1 130 150 480V 250A 35,000MBSWH-16K-S3-KK 30.1 x 10.8 x 42.1 130 160 480V 250A 35,000MBSWH-22K-S3-KK 36 x 12.8 x 48.1 280 225 480V 350A 35,000MBSWH-30K-S3-KK 36 x 12.8 x 48.1 280 300 480V 500A 65,000MBSWH-37K-S3-KK 36 x 12.8 x 48.1 280 375 480V 600A 65,000MBSWH-50K-S3-KK 36 x 12.8 x 48.1 280 500 480V 800A 65,000* -KK: Keyed Mechanical Interlock Key (2-key)-KS: Solenoid Key (SKRU)