E6581268- 16 -Examples of Instance 100/150StopInstance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex.1, 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0x0000Output Instance 100 3, 2 - - - - - - - - - - - - - - - - -1, 0 0 1 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0x4800Input Instance 150 3, 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0x0000Forward running 60HzInstance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex.1, 0 1 1 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0xC400Output Instance 100 3, 2 0 0 0 1 0 1 1 1 0 1 1 1 0 0 0 0 0x17701, 0 0 1 1 0 0 1 0 0 0 0 0 0 0 0 0 0 0x6400Input Instance 150 3, 2 0 0 0 1 0 1 1 1 0 1 1 1 0 0 0 0 0x1770Reverse running 60HzInstance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex.1, 0 1 1 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0xC600Output Instance 100 3, 2 0 0 0 1 0 1 1 1 0 1 1 1 0 0 0 0 0x17701, 0 0 1 1 0 0 1 1 0 0 0 0 0 0 0 0 0 0x6600Input Instance 150 3, 2 0 0 0 1 0 1 1 1 0 1 1 1 0 0 0 0 0x1770Preset speed 1 with forward running (sr1)Instance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex.1, 0 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 0x8401Output Instance 100 3, 2 - - - - - - - - - - - - - - - - -Input Instance 150 1, 0 0 1 1 0 0 1 0 0 0 0 0 0 0 0 0 0 0x6400(sr1 is set 5Hz.) 3, 2 0 0 0 0 0 0 0 1 1 1 1 1 0 1 0 0 0x01F4Fault reset ***Instance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex.1, 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0x2000Output Instance 100 3, 2 - - - - - - - - - - - - - - - - -About the other command, refer to the Communications Function Instruction Manual (E6581222) section 8.1.*** Fault reset works only 1 time when 0 -> 1.