Document Number: 60910-000 1ASD-MTG-KITQ9 Installation ProcedureThe Q9 ASD may be controlled from a remotely-mounted Electronic Operator Interface (EOI).The remotely-mounted EOI can operate up to 9 feet away from the ASD.An EOI extender cable is required for remote mounting and is included with the ASD-MTG-KITQ9.EOI-to-ASD functionality is the same whether the EOI is mounted to the ASD power unit or mountedremotely.Required Remote-mount HardwareEOI Remote-Mount Assembly• ASD-MTG-KITQ9 Assy.Mounting Precautions• The ambient operating temperature range of the EOI is 14° – 104° F (-10 – 40° C).• Mount the unit securely in a well ventilated area that is out of direct sunlight.• Select a mounting location that is easily accessible by the user.• Avoid installation in areas where vibration, heat, humidity, dust, metal particles, or high levels ofelectrical noise (EMI) are present.• Do not install the EOI where it may be exposed to flammable chemicals or gasses, or any fluids(i.e., water, solvents, etc.).Remote EOI InstallationInstallation, operation, and maintenance shall be performed by Qualified Personnel Only.Read and adhere to the Safety Precautions and Warnings of the Installation andOperation Manual of the ASD.1. At the Remote EOI mounting location, identify and mark the locations of the 4.56” by 4.44” holeand the four 7/32” screw holes (see Figure 1).2. Cut the 4.56” by 4.44” rectangular mounting hole.3. Drill the four 7/32” screw holes for the four mounting studs of the mounting plate of the RemoteEOI.4. Attach and secure the Remote EOI to the front side of the mounting location using the four #10 flatwashers, #10 split lock washers, and the 10-32 hex nuts.5. Remove the front panel assembly of the ASD — Using a flat screwdriver, release the upperretaining tabs of the EOI panel then pivot the EOI assembly away from the ASD and lift (seeFigure 2).6. Remove the Display Module from the panel assembly of step 5 — discard the panel assembly.