User’s Manual 49PART 2 DA264 5. I/O Allocation and Programming1 to 5V / 4 to 20mA range:D/A conversion data Output voltage/currentHexadecimal Integer 1 to 5 V 4 to 20 mA ResolutionUpper limit H337F 13183 +5.1196 V +20.479 mA: : : :Full scale (positive) H3200 12800 +5 V +20 mA: : : :H0001 1 +1.0003125 V +4.00125 mA0 H0000 0 1 V 4 mA: : : :Lower limit HF380 -3200 0 V 0 mA0.3125 mV / bit1.25 μA / bit4 to 20mA range:A = 1.25 × D + 4000D: Digital dataA: Analog signal (μA)1 to 5V range:A = 0.3125 × D + 1000D: Digital dataA: Analog signal (mV)H8000-327680 H7FFF32767Analog output value H320012800Digital data+5V(+20mA)+1V(+4mA)HF380-3200H337F13183+5.1196V(+20.478mA)Lower limitUpper limitCTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net