33 / 176Siemens Web server OZW772... V6.0 CE1C5701enBuilding Technologies Commissioning 2015-10-12Path: Home > 0.2.150 OZW772.xx > Settings > Consumption data > Receiver >E-mail receiver 1…2· The settings configure sending the consumption data file per e-mail.· The e-mail signature (sender name, address, etc.) is set under "Settings >Communication > E-mail".· The settings are independent of the settings for the message receiver (SectionMessage receiver 1…4).Data point Explanation, exampleE-mail addressDefault val: mailReceiver@example.comSetting val: max. 49 charactersThe setting must match the consumption datareceiver’s e-mail address.—Transmit intervalDefault val: NeverSetting val: Never, daily,weekly, monthlyThe send interval sets how often consumptiondata is sent to the e-mail receiver. The setting"Never" corresponds to "turned off".—File formatDefault val: .xmlSetting val: (empty), .xml, .csvThe file format sets the format of the e-mailattached for consumption data. Two files areattached if both formats are selected. No file isadded is the setting is empty.—Test receiverDefault val: ---Setting val: ---, Trigger"Test receiver" tests the connected to theselected receiver.—On send interval:· It is generally sent as soon as the data collection is completed for the WebServer.· Daily means between 5 and 10 am.· Weekly means Sundays (between 5 and 10 am).· Monthly refers to the third day of the month (between 5 am and 10 pm).In the case of "Annual allocation", "monthly" can be selected: The 11 additionale-mails with attached consumption data files are available for backup purposesor to provide precise billing by the month in the event of a change of renters.2.5.3.7 Energy indicatorThe menu "Energy indicator" is displayed if the controller is connected to the WebServer that supports the Energy indicator. The menu is hidden if no devices of thistype are connected.2 e-mail receivers can be defined for the Energy indicator. Settings are made at:Path: Home > 0.2.150 OZW772.xx > > Settings > Energy indicatorThe descriptions are available in Section 7.5 "E-mail with "Energy indicator" for theplant".Visibility of the "Energy indicator" can be defined:Path: Home > 0.2.150 OZW772.xx > Settings > Energy indicatorThe descriptions are available in Section 7.2.5 "Energy indicator" visibility".ReceiverNotesNotesE-Mail receiver 1…2Visibility