7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) ñ INSTRUCTION MANUAL Page 85H: Parameters2.6.3. Linearization Volume (default 100.0)The maximum volume of the tank. Units are defined in Primary Value units. Anyvolumetric units can be chosen, because the volume calculation is based on themaximum volume, and scaled according to the vessel shape selected. If no vesselshape is entered, the default is 100, and the reading will be a percentage value.For readings in volumetric units instead of percentage values, enter the vesselvolume corresponding to High Calibration Point.2.6.4. Dimension A (default 0.0)The height of the vessel bottom (in level units) when the bottom is conical,pyramidal, parabolic, spherical, flat sloped, cylindrical, or spherical. See page 84for an illustration.1. Go to Input > Sensor Calibration > Unit (level) and select desiredlevel units.2. Key in the height of the vessel bottom in level units.244 flat sloped bottom linearization volume,dimension A245 parabolic endhorizontal cylinderlinearization volume,dimension A, dimension L247universal linear(level/volume/flowbreakpoints)linearization volume (flow),level (head) breakpoints,volume (flow) breakpoints1. Enter handheld programmer value.Hand programmer values Range: 0.0000 to 99999Related Parameters Low Calibration PointHigh Calibration PointHand programmer values Range: 0.0000 to 99999 in units (P005)Related Parameters Tank ShapeEnter 1 Tank Shape (cont’d) Description Also requiredAA L