Functions9.7 Monitoring functionsSIPLUS HCS4200 PROFINET/PROFIBUS DP148 Operating Instructions, 07/2019, A5E35066204A/006Line voltage monitoring POM4220 Lowend, POM4220 Midrange phase angle control andPOM4220 FlexibleThe monitoring function is only available for these modules if a PM U/I is plugged in.Permitted line voltage range:● POM4220 Lowend: 207 V to 253 V AC● POM4220 Midrange phase angle control: 207 V AC to 300 V AC● POM4220 Flexible:Monitoring for the smallest and greatest value of the POM used(max. 45 V - 10 % to 300 V)Line supply voltage monitoring POM4220 HighendThe measured values of the POM are used for monitoring. The permitted voltage range is:● 207 to 300 V AC for:– Connection between phase and neutral conductor– 2-pin connection between phase and neutral conductor● 360 to 520 V AC for:– Connection between phase and phase– 2-pin connection between phase and phase– Economy circuitLine supply voltage monitoring POM4320The measured values of the POM are used for monitoring.The permitted line voltage range is 360 V AC to 520 V AC.9.7.4 Monitoring of the 24 V DC supply voltageThe 24 V DC supply voltage is monitored on the CIM. If the 24 V fails, the power outputs ofthe POMs are automatically deactivated. There is no manufacturer-specific diagnosticsalarm in the case of failure of the 24 V supply. Instead, the PROFINET/PROFIBUS controllerdetects and signals failure of the HCS system or individual modules.