Communications10.2 Acyclic data exchangeSIPLUS HCS4300 PROFINET/PROFIBUS DP138 Operating Instructions, 10/2019, A5E35452705A/005Data record 200 "Measured values"The data record describes an HCS function and addresses the HCS.Byte MeaningData POM 1 0 Internal temperature1 Reserved2, 3 Frequency with one decimal place4, 5 Voltage measured value L1/L12 with one decimal place6, 7 Voltage measured values L2/L23 with one decimal place8, 9 Voltage measured value L3/L31 with one decimal placeData POM 2 … …… … ...Data for POM24… ...Definition is via an array [1 to 24] with one element of the "Structure" type. This comprisestwo elements of type "Byte" and four elements of type "Word".The POM number corresponds to the array index.The length of the data record corresponds to the number of POMs that are used.Data record 201 "Versions"The data record describes an HCS function and addresses the HCS.Byte MeaningCIM / PM 0 to 3 FW version of CIM fieldbus controller4 to 7 FW version of CIM HCS master8 HW version of CIM9 HW version of PM10 to 13 FW version of PMPOM 1 14 to 17 Firmware version POM 118 Hardware version triac POM 119 Hardware version fuse POM 1POM 2 … …… … …POM 24 … …All firmware versions contain one element of type "Char" and three elements of type "Byte".The hardware versions are all of type "Byte".Definition of the POM versions is via an array [1 to 24] with one element of type "Structure".The POM number corresponds to the array index.The length of the data record corresponds to the number of POMs that are used. The entryfor CIM with PM is always available, even if the PM is not plugged in.