2 EngineeringMonitoring of Remote Measurement PointsEntry ID: 109739240, V3.0, 06/2021 27© Siemens AG 2021 All rights reserved30. Select the measurement type of your analog level sensor. The SITRANSProbe LU150 sensor must be set to "Current (2-wire connector)".303131. Enter the settling and integration time as well as the smoothing of the signal ofyour sensor. The following settings are recommended for the SITRANS ProbeLU150 sensor:– Settling time: 30,000 ms– Integration time: 40 ms– Smoothing: WeakNote Note that (settling time + integration time) * smoothing factor must not be longerthan the update mode cycle.32. Enter the sensor and process values for your application. In this applicationexample, a sensor signal of 20 mA corresponds to a level of 10,000 m³.33. Select the digital input "enableReadFillLevel (DI1)" as the "enable signal".