1Installation InstructionsModel PAL-1Parallel PrinterP/N 315-092408-14Siemens Industry, Inc.Building Technologies Division8 Fernwood RoadFlorham Park, New Jersey 07932Siemens Canada LimitedBuilding Technologies Division2 Kenview BoulevardBrampton, Ontario L6T 5E4 CanadaOperationThe model PAL-1 from Siemens Industry, Inc. allows the connec-tion of an ITE Centronics parallel printer to the Siemens FireFinder-XLS, MXL, FireFinder-NCC, FC2025, FC2050, FC922, FC924,Desigo CC and Cerberus DMS systems. See the manufacturer'sinstallation manual for self diagnostics.The PAL-1 printer can be used with control panel models XLS,FC2025, FC2050, FC922, FC924, NCC, Desigo CC, and Cerberus DMSManagement Systems in UL864 and ULC-S527 installations. The PAL-1printer can be used in UL2572 installations, Control and Communication Units for Mass Notification. Forsupplementary use only, the NCC and PAL-1 may be connected to the UL1076 approved XLS and MXLcontrol panels.InstallationUPS Standby PowerThe PAL-1 printer requires a standby power source in the event of the loss of primary input power (ACmains). Refer to Figure 2 for the connection of a UPS to meet this requirement.Figure 1PAL-1 Printer1H2GND3N4H5N9H10GND11N6H7GND8N120 VACUTILITY INPUTPOWER120 VACUTILITYPOWERSOURCEDO NOTUSEPOWER TOPRINTER120 VACSEE NOTE 4120 VACINPUTPOWERAFTER FILTER120 VACOUTPUT OFTHE UPSACINPUTFAILTERMINAL BLOCKLOCATED ONUPS SYSTEMCONTROL BOARDBATTERYFAIL1NO2C3NC4NO5C6NCDO NOTUSETO TRI-60/B6/S OR HTRI-S/-D/-R INPUTTERMINALS. PROGRAM AS NORMALLY OPENTROUBLE CAUSING INPUT IN CSG-M (AccuLINK)OR ZEUS AND FPI-32 OR DPU, AS APPLICABLE.REFER TO TRI-60 INSTALLATION INSTRUCTIONS,P/N 315-092329, THE TRI-B6 INSTALLATIONINSTRUCTIONS, P/N 315-093315,OR THE HTRI-S/-D/-R INSTALLATIONINSTRUCTIONS, P/N 315-033300 OR 315-049075,AS APPLICABLE.OR THE TRI-SINSTALLATION INSTRUCTIONS, P/N 315-096242 OR315-049481,Figure 2UPS Wiring DiagramNOTES:1. All wires 14 AWG min, 600V insulation.2. Wiring to the printer and must be 14 AWG min., 600V insulation in conduit, and located in the same room as thecontrol panel.3. Use the UPS ICS Lifeline Model 9300057.4. Standby Power requirements: 120 VAC, 3A for 24 hours.