42PAD-4 Operation, Installation, and Maintenance Manual5.1.4 Setting the AC Power Fault ReportingDelay on the Global Trouble RelayRefer to Figure 5-6 to set the AC Power FaultReporting on the Global Trouble Relay to one ofthe following selections:• AC Power Fail will never be reported. Notpermitted by UL 864. Refer to page 39.• AC Power Fail reporting will not be delayed.Not permitted by UL 864. Used for localsystems. Refer to page 39.• AC Power Fail reporting will be delayed 60minutes.• AC Power Fail reporting will be delayed 180minutes.Note: Switch settings on Switches 9 and 10 donot affect the operation of the AC Fail Relay.The AC Fail Relay will activate immediatelyupon low or no AC power under all conditions.In ULC configuration, DIP Switch 9 and 10 aredisabled and AC Power Fail Reporting will notbe delayed.910 8 7 6ONOFFSwitch 9 OFF & Switch 10 OFF:AC Power Fail will never bereported.Not permitted by UL 864. Refer topage 39.Switch 9 ON & Switch 10 OFF:AC Power Fail reporting will notbe delayed. Not permitted by UL864. Refer to page 39.Switch 9 OFF & Switch 10 ON:AC Power Fail reporting will bedelayed 60 minutes.Switch 9 ON & Switch 10 ON:AC Power Fail reporting will bedelayed 180 minutes.910 8 7 6910 8 7 6910 8 7 6** If this option is chosen, the PAD-4 must always bemonitored via the AC Fail relay.Figure 5-6Setting DIP Switch 9 and 105.2 JUMPER SETTINGSFactory settings are shown. See Figure 2-5 forthe location of these jumpers.Note: Changing settings for J4-J8 also affectthe settings for S1 DIP switches 1-3. Also theNACs must be configured as either all Class Aor all Class B.123J4 - NAC 1-2 Configuration(J5 must be set the same) Class BClass A123J5 - NAC 1-2 Configuration(J4 must be set the same) Class BClass A123J7 - NAC 3-4 Configuration(J8 must be set the same) Class BClass A123J8 - NAC 3-4 Configuration(J7 must be set the same) Class BClass A123J9 - Ground DetectionConfiguration EnabledDisabled123J13, J14 - Input 2 Emulation Setting(J14 must be set the same as J13) SwitchPanel123J10 - Battery ChargerConfiguration DisabledEnabled123J11, J12 - Input 1 Emulation Setting(J12 must be set the same as J11) SwitchPanelJ4 - NAC 1-2 Configuration(J5 must be set the same)J2 - UL-ULC Configuration(Jumper set for ULC operation)ULCJ2Figure 5-7Jumper Configuration Settings