K3R070 Mimic Display board (superseded by K3R071)205Building Technologies 001260_k_en_--.docFire Safety & Security Products 02.200548.5 Important components1234567X1X48K1F1S1K2ST1F12A100ST2ON 1Legend:1 48 plug-in connectors, 2-pin: 2-wire cable (cable set Z3I520 = 12 cables) toLEDs in Mimic display2 Connector "ST1" / "ST2": Connection of data bus via flat cable3 Fuse 'F1' 0.4 A/T: Supply input 9...45 VDC4 Programming switch "S1": Equipment address settingFunction Programming switch S1No. S1-1 S1-2 S1-3 S1-40Test procedure:In this setting all inputs are briefly activated in sequence. off off off off1 Equipment address 1 on off off off2 2 off on off off3 3 on on off off4 4 off off on off5 5 on off on off6 6 off on on off7 7 on on on off8 8 off off off on"S1-1...4" are set to "off" at the factory5 Plug-in terminals "K1", 4 pin: Power supply 9...45 VDC6 Plug-in terminals "K2", 6 pin: Connection of data bus instead of flat cable7 Resistor array (assembled ex work / must be assembled only for one device)