4.5 - exhibit LF4.5.1 - Wire sizesPower supply (copper only, over-voltage category III - IEC 60664)16LJ208 V 460 V 400 VCurrentdrawn, AWiresection,mm2screwsizetighteningtorque,NmCurrentdrawn, AWiresection,mm2screwsizetighteningtorque,NmCurrentdrawn, AWiresection,mm2screwsizetighteningtorque,Nm11 13.9 2.5 M5 2.2-2.8 6.7 2.5 M5 2.2-2.8 6.7 2.5 M5 2.2-2.812 13.9 2.5 M5 2.2-2.8 6.7 2.5 M5 2.2-2.8 6.7 2.5 M5 2.2-2.813 13.9 2.5 M5 2.2-2.8 6.7 2.5 M5 2.2-2.8 6.7 2.5 M5 2.2-2.814 13.9 2.5 M5 2.2-2.8 6.7 2.5 M5 2.2-2.8 6.7 2.5 M5 2.2-2.821 18.8 4 M5 2.2-2.8 9.0 2.5 M5 2.2-2.8 9.2 2.5 M5 2.2-2.822 18.8 4 M5 2.2-2.8 9.0 2.5 M5 2.2-2.8 9.2 2.5 M5 2.2-2.823 19.0 4 M5 2.2-2.8 9.1 2.5 M5 2.2-2.8 9.3 2.5 M5 2.2-2.824 19.0 4 M5 2.2-2.8 9.1 2.5 M5 2.2-2.8 9.3 2.5 M5 2.2-2.831 23.5 4 M5 2.2-2.8 11.1 2.5 M5 2.2-2.8 11.5 2.5 M5 2.2-2.832 23.5 4 M5 2.2-2.8 11.1 2.5 M5 2.2-2.8 11.5 2.5 M5 2.2-2.841 23.5 4 M5 2.2-2.8 11.1 2.5 M5 2.2-2.8 11.5 2.5 M5 2.2-2.842 23.5 4 M5 2.2-2.8 11.1 2.5 M5 2.2-2.8 11.5 2.5 M5 2.2-2.851 23.5 4 M5 2.2-2.8 11.1 2.5 M5 2.2-2.8 11.5 2.5 M5 2.2-2.852 23.5 4 M5 2.2-2.8 11.1 2.5 M5 2.2-2.8 11.5 2.5 M5 2.2-2.853 23.5 4 M5 2.2-2.8 11.1 2.5 M5 2.2-2.8 11.5 2.5 M5 2.2-2.8other signals (copper only, over-voltage category II - IEC 60664)Wire size screw size tightening torque1 mm 2 M3.5 1.4-1.8 Nm |