-1-SANYO AIR CONDITIONING PRODUCTSDUCTLESS SPLIT SYSTEM AIR CONDITIONERSSPECIFICATIONS - SECTION 15700Covers Sanyo System Models > 09KS51, 09KLS51, 12KS51, 12KLS51, 18KS52, 18KLS52,(See plans for specified model(s) & details)DUCTLESS SPLIT SYSTEM AIR CONDITIONERS - WALL MOUNT TYPE1) GENERAL SPECIFICATIONSFurnish & install a Sanyo manufactured Ductless, Split System Air Conditioner(s), consisting ofan indoor, high wall mounted evaporator/blower section & matching outdoor condensing section.System(s) shall bear the ARI label showing that the system(s) is ARI 210 or 240 & 270 Certified.Systems shall be listed by CSA International and bear the C-CSA US label. Matching systemsshall meet or exceed the minimum, Federally mandated Seasonal Energy Efficiency Rating(SEER) of 10 as certified by the ARI testing programs. System(s) indoor & outdoor units willoperate at sound levels equal to or below specified system(s) (see plans). Installation & OwnersManuals shall be provided with each system.Matching indoor & outdoor sections shall be connected by deoxidized, annealed refrigerant coppertubing, type “L”, cleaned & capped. All systems shall have flared refrigeration connections onboth indoor & outdoor sections. Size & insulate tubing according to manufacturer’s specifications.System(s) indoor & outdoor sections shall be completely factory assembled & wired, with a pre-charge of refrigerant. A single power source shall provide voltage to both the outdoor & indoorunits. Electrical wire & connections to outdoor section, and between indoor & outdoor section(s),shall be sized, installed & grounded by the installer in conformance with the National ElectricalCode (N.E.C.), local codes, as well as, manufacturer’s instructions.System(s) shall be equipped with a microprocessor control system, utilizing an infrared remotecontroller with LCD display that provides access to all system functions, and transmits programsto the indoor microprocessor every 5 minutes. Infrared remote controller shall be capable ofoperating system mounted up to 26’ from the indoor section, according to manufacturer’srecommendations & instructions. System(s) shall have the capability of continuous operation inthe case of a lost or damaged remote controller, utilizing a factory installed, integral manualswitch in conjunction with the system microprocessor.1A) System Infrared Remote Controller Functions will include: system mode selection,programmable temperature control, 24hour programmable timer, one (1) hour off timer,automatic three (3) speed indoor fan speed control, constant fan speed selection, night setbackmode, automatic sweep/flap control, multiple system control using a single controller.1B) System Features will include: Sanyo high efficiency, rotary compressor, cap tube refrigerantcontrol, indoor coil freeze protection, built-in auto restart after power failure, short cycle time