Installation21!,,/+&10Minimum clearances for the outdoor unitWhen installing 1 outdoor unitUnit : inch (mm)11.81 (300) ormore59.06 (1500) ormore11.81 (300)or more23.62(600)or more11.81(300)or more78.74 (2000)or more59.06 (1500)or more23.62 (600)or more 11.81 (300)or more59.06(1500)or more11.81(300)or moreWhen installing more than 1 outdoor unitUnit : inch (mm)59.06 (1500)or more 23.62 (600)or more 118.11 (3000)or more 118.11 (3000)or more11.81 (300)or more23.62 (600)or more 23.62 (600)or more59.06 (1500)or more 11.81 (300)or more23.62 (600)or more23.62 (600)or more59.06 (1500)or more23.62 (600)or more 23.62 (600)or more23.62(600)or more11.81(300)or more11.81 (300)or more11.81 (300) or more11.81 (300) or more19.69 (500) or more 19.69 (500) or moreCAUTION• The outdoor unit must be installed according to thespecified distances in order to permit accessibilityfrom each side, to guarantee correct operation,maintenance, and repair of the unit.The components of the outdoor unit must bereachable and removable under safe conditions forpeople and the unit.WARNING• Should adopt bar type louver. Don’t use a type of rainresistance louver.[Bar type louver] [Rain resistance louver]• Louver specifications.– Angle criteria : less than 20°– Opening ratio criteria : greater than 80%