E-39Pattern ControlPattern1 ▶ No external input (Factory default setting)When you input contact control signal in port 1, there will be no response.Pattern2▶ Level input (Emergency stop)1. If the contact control signal is changed to ON, emergency stop status and all theindoor units are given ‘Stop’ command, and controlling using remote controller isimpossible.2. During the emergency stop, the BACnet Gateway will ignore any request from theupper controllers.3. During the emergency stop, the BACnet Gateway will ignore previously setschedules.4. When the contact control signal changes from ON to OFF, DVM goes into normaloperation status and returns to the remote control status before emergency stop.5. Even if the contact control signal of port 1 changes from ON to OFF, there will be nochange to the indoor unit.6. When you input contact control signal in port 2, there will be no response.Pattern3▶ Level input (Operation/Stop, Remote control Enable/Disable)1. If the contact signal of port 1 changes from OFF to ON, all indoor units will be given‘Operation‘ command.2. If the contact signal of port 1 changes from ON to OFF, all indoor units will be given‘Stop‘ command.3. If the contact signal of port 2 is OFF, you cannot control all indoor units usingremote controller.4. If the contact signal of port 2 changes from OFF to ON, you can control all indoorunits using remote controller.5. If the contact signal of port 2 changes from ON to OFF, you cannot control all indoorunits using remote controller.6. Control command from the upper controller will be operated regardless of thecontact point status.7. DVM system control using Schedule control will be operated regardless of thecontact point status.Pattern4▶ Pulse input (Operation/Stop)1. Valid pulse duration for input signal is 0.5~1.0 second.BACnet Gateway ignores the signal which has shorter than 0.5 second duration,longer than1.0 second Pulse width.2. When Pulse input signal is ON in Port 1. all indoor units will be given ‘Operation‘command.3. When Pulse input signal is ON in Port 2. all indoor units will be given ‘Stop‘command.4. DVM control command from the upper controller will be operated regardless ofPulse input signal.5. DVM system control using Schedule control will be operated regardless ofPulse input signal.Contact point control patternNASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 39 2013-04-25 오전 10:14:39