Setting the address of ERV (MAIN/RMC)1 Check whether power is supplied to the ERV or not- When the power is not supplied to the ERV, there should be additional power supply to it2 Depending on the installation condition of the ERV, each ERV's address (MaIn/RMC) should be set3 Set the ERV's address (MaIn/RMC) by using a remote controller- Initial address of the ERV is set as follows; "MaIn:0, RMC:0"- Set MaIn and RMC address only when it is necessary When ERV interface module assigns address automatically,setting the MaIn address is unnecessary and even though the MaIn address is set, the ERV will follow the addressassigned by the ERV interface module- Default value will be maintained when you input the numbers that shouldn't be set on each SEG (If you input anynumber in SEG13~24, the value will be ignored )- If you input any value on the SEG with "no function", it will be ignored4 Use a wired/wireless remote controller to set the option When setting the option with wireless remote controller,receiving module for remote controller is embedded in PBa so there's no need for connecting extra paneloption No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXXOption SEG1 SEG2 SEG3 SEG4 SEG5 SEG6Description Page Mode Setting main addressno function10-digit of ERV The unit digit of anERVIndicationand DetailsIndication Details Indication Details Indication Details Indication Details Indication Details0 a0 no main address0~4 10-digit 0~9 Unit digit1 address settingmodeOption SEG7 SEG8 SEG9 SEG10 SEG11 SEG12Description Pageno functionSetting RMC addressno functionGroup channel Group addressIndicationand DetailsIndication Details Indication Details Indication Details Indication Details10 no main addressRMC1 0~2 RMC2 0~F1 address settingmodeExample) To set "MaIn address: 3/ Group channel: 1/ RMC address: B", you may set the option as shown in the following table(excluding SEG1 and SEG7 which is page option)SEG1 SEG2 SEG3 SEG4 SEG5 SEG60 a 1 - - 3SEG7 SEG8 SEG9 SEG10 SEG11 SEG121 - 1 - 1 B• Main address can be set from 0~47 only and if any other values are set, 'communication error' will occur• If you set the SEG3 as 0, the ERV will maintain the existing main address even if you input the option value ofSEG6• If you set the SEG9 as 0, the ERV will maintain existing RMC address even if you input the option value ofSEG11~12CAUtIoNENGLISH-3503 otHERS