119View mode display▶ Press and hold K3 and K4 for 3 seconds to enter the view mode.▶ Press K3 to change view mode in order of the table.▶ Press K4 to change view mode in reverse order of the table.▶ Cancelling view mode display- Press and hold K3 for 3 seconds.Basic segment displaySEG1 SEG2 SEG3 SEG4 SEG5 SEG6 RemarksWater In 0 1 - 0 5 0 Ex) -5 °CNumber ofpress KEY operation SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Remarks1 time Water In 0 1 - 0 5 0 ex) -5 °C2 times Water Out 0 2 - 1 1 0 ex) -11 °C3 times Outdoor temperature 0 3 - 1 1 2 ex) -11.2 °C4 times High pressure 0 4 2 9 3 ex) 29.3 kgf/cm 2G5 times Low pressure 0 5 0 7 5 ex) 7.5 kgf/cm 2G6 times Comp 1 currentfrequency 0 6 1 1 0 ex) 110 Hz7 times Comp 2 currentfrequency 0 7 1 1 3 ex) 113 Hz8 times Discharge1 temperature 0 8 1 0 1 ex) 101.8 °C → 101(Drop)9 times Discharge2 temperature 0 9 1 0 1 ex) 101.8 °C → 101(Drop)10 times Top1 temperature 1 0 1 0 1 ex) 101.8 °C → 101(Drop)11 times Top2 temperature 1 1 1 0 1 ex) 101.8 °C → 101(Drop)12 times Total Suctiontemperature 1 2 - 1 1 2 ex) -11.2 °C8. Key Options8-1. Setting hydro controller optionHYDRO-UNIT_MODULE_CHILLERK1 K2 K3 K4 K5 K6K1 K2 K3 K4 K5 K688-SEG DISPLAYTACT S/WDIP S/W