© 2011 Racktivity NV 30/52Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27Device SettingsThe Device Settings give access to EnergySwitch identificationo Device name: the name of the EnergySwitcho Rack name: the name of the rack where the EnergySwitch is locatedo Rack position: the identifier of the position in the rack UPS Integrationo Uninterruptible Power Supply: select UPS to connect to (enables the UPS tab) User account settings (see the User Account Overview chapter)o Admino Restricted usero Guest TFT settingso TFT timeout: the idle time in minutes after which the TFT goes into standbyo TFT display lock: when checked the TFT (and buttons) cannot be used to changesettings. All changes must be made through the website. Temperatureo Temperature unit: degrees Celsius (°C) or Fahrenheit (°F) Clock settings (see the Network Time Protocol (NTP) chapter)o Date & Time Settings: The real-time clock dialog features several options.Uncheck the Use NTP checkbox to be able to set a custom date & time. Uncheckthe Use default NTP checkbox to not use an NTP server from pool.ntp.org andenter the custom IP address into the NTP address field.Note: Making changes to the date/time settings might clear all logged data!ThresholdsThresholds can be configured and used so that you are notified through SNMP at certain events.Many of the EnergySwitch’s parameters have settable thresholds. To configure a specificthreshold, open the tab where the appropriate parameter is shown.At least the following parameters have one or more settable thresholds: Amperageo path: Power > Current Wattageo path: Power > Power Voltageo path: Environment > Voltage Ambiento path: Environment > Ambient